The Outback Power System EnergyCell 800RE is a 32.4 kWh, 48 volt (676 amp hour @ 24 hour), High Capacity VRLA-AGM battery with rack system and interconnects. The EnergyCell RE high capacity battery bank is designed to provide battery backup and excellent performance in grid-tied, grid-interactive and off-grid residential and light commercial applications for an uninterrupted power supply. This battery bank is a part of the EnergyCell RE High Capacity Series from Outback. The EnergyCell RE high capacity battery family offers an ideal solution for large capacity Valved Regulated Lead Acid (VRLA) battery requirements.
The EnergyCell RE high capacity battery has a steel can module design concept, with its integral racking system, providing a cost effective battery system with a compact, quick and simple installation process. The EnergyCell RE AGM technology incorporates an enhanced cell design with a superior racking system. The enhanced cell incorporates thicker positive plates for longer life. The welded/epoxy dual post seal design provides the highest integrity seal in the industry. The large copper post design also enhances the high rate performance. Optimized to work seamlessly with OutBack power conversion equipment. For backup power energy storage, the EnergyCell RE 800RE battery is the ideal choice for superior performance and longevity, and is backed by a 3-year warranty. Order online or by PHONE 888-498-3331
- Designed for off-grid or grid-tied battery backup residential and light commercial applications
- 1,800 cycles @ 50% depth of discharge
- Space-saving 4x6 standard 48V system configuration
- Battery frame design allows for maximum heat dissipation
- 100% out of box initial battery capacity
- VRLA-AGM technology means 99% gas recombination efficient, no periodic watering of cells, no re-torquing of terminal connections, and no equalization charge under standard operating conditions
- Steel module design, cells factory installed in permanent steel modules with 1 or 2 cells per can, allows for ease of replacement
- Standard top termination, optional side termination
- Clear flame retardant front safety shields allow for easy visual
- inspection without removal of cells
- Flame-retardant battery jars for increased safety
- OPTICS RE connectivity means real-time access to critical battery performance data
- Batteries and power electronics can be installed in the same area
- Optimized to work seamlessly with OutBack power conversion equipment
Parts / Specifications
Nominal Voltage Per Cell: |
2V |
Capacity 20Hr Rate (1.75VPC): |
672 Ah |
Capacity 24Hr Rate (1.75VPC): |
676 Ah |
Capacity 100Hr Rate (1.75VPC): |
810 Ah |
Watts Per Cell 15min Rate (1.67VPC): |
1230 watts |
Nominal Voltage Per System: |
48VDC |
Cycle Life (50% DOD, 1.75VPC): |
1800 cycles |
Absorb Voltage (25°C): |
55.6VDC |
Absorb Time: |
2 hours |
OCV Per Cell Limit: |
2.05 |
Initial Charge Voltage Per Cell: |
2.27 V |
Float Voltage Per Cell (77°F/25°C): |
2.25 V |
Float Voltage Per Cell (95°F/35°C): |
2.21 V |
For Cycle Service the Absorb Voltage is the Equalization Voltage*** (69.8 to 89.6°F/21 to 32°C): |
2.32 V |
Maximum Charge Current (A): |
148.75 Amps |
Shelf Life (77°F/25°C): |
6 months |
Short Circuit Current (A): |
4728 Amps |
Internal Resistance (micro Ohm): |
441 |
Hardware Specification (Intercell Connects): |
M8 bolt, lock and flat washer |
Weight Per Cell: |
114.3 lbs / 51.8 kg |
Self-Discharge Time: |
6 months @ 25°C |
Terminal Type: |
M8 bolt, lock, flat washer |
Terminal Hardware Initial Torque: |
88in-lbs |
Dimensions (D x W x H): |
23.50 × 39.40 × 43.44 inches |
Weight: |
2262 lbs |
Warranty: |
3 years |
48V Standard System Configuration: |
6w x 4h |